
SPEDLPX0205REN
22
DIALOG PLUS
Table 3: input voltage
Battery LED bar
Input Voltage
1 2 3 4 5
190V~200V *
200V~230V * *
230V~250V * * *
250V~260V * * * *
>260V * * * * *
Table 4: load level
Load LED bar
Load level
25 50 75 100
!
0~5%
5~25%
*
25%~50%
* *
50%~75%
* * *
75%~102%
* * * *
>102%
* * * * *
* LED illuminated steady
Overloads on the UPS
The following table shows how the UPS reacts when overloads occur during mains or battery operation, and
indicates the time that the UPS will continue to supply power to the load.
OVERLOAD LEVEL
OVERLOAD TIMES
(from mains)
OVERLOAD TIMES
(from battery)
102% < Load ≤ 109%
Switches to bypass after 30 min
Shutdown after 30 min (if battery
back up time allows)
110% <= Load ≤ 130%
Switches to bypass after 30 sec Shutdown after 30 sec
130% < Load ≤ 150%
Switches to bypass after 10 sec Shutdown after 10 sec
Load > 150% Switches to bypass after 0.5 sec Shutdown after 0.5 sec
Kommentare zu diesen Handbüchern