SPEDLPX0205REN
18
DIALOG PLUS
> 8.3 Configuration software
Configuration Software
UPSTools software enables the user to configure the UPS, and provides a full view of the system
parameters and status through the RS232 serial port.
Refer to the paragraph UPS Configuration for a list of the configurable values available.
UPS Configuration
The following table lists all of the possible configurable values available so as to best adapt the UPS to the
user requirements. The configuration can only be modified using the UPSTools software provided.
FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS
Automatic Restart
Automatic restart when
the mains power supply
returns
Enabled.
• Disabled
• Enabled
Battery low alarm
Remaining battery charge
level setting for the
battery low alarm
3 min.
• 1 – 99 in steps of 1 minute
Output frequency
Enables the user to select
the output frequency.
50Hz
• 50Hz
• 60Hz
• Auto(the UPS will set the output to
match the input frequency either 50 or
60 Hz)
Output voltage
Enables the user to select
the output voltage
230 Vac
• 220 Vac
• 230 Vac
• 240 Vac
Bypass voltage
threshold
Selects the voltage range
accepted for switching
over to the bypass
Low: 180V
High: 264V
• Low: 180 – 200 in steps of 1V
• High: 250 – 264 in steps of 1V
Battery capacity
Enables the user to set
the capacity of battery
Standard:
7.2Ah
ER: 65Ah
The user must set the capacity of the battery
if the actual capacity is different from the
default value.