4.8 Assembly of the gas train
³ The gas train is type-approved according to standard EN 676 and is sup-
plied separately from the burner, with the code indicated in Appendix B.
³ The gas train can enter the burner from the right or left side, depending
on which is the most convenient, see Fig. 19.
³ The gas train must be connected to the gas attachment 1)(Fig. 19) with
the flange 2), the gasket 3) and the screws 4) supplied with the burner.
³ The gas solenoids must be as close as possible to the burner, to ensure
that the gas reaches the combustion head within the safety time of 3 s.
³ Ensure that the maximum pressure necessary for the burner is included
in the calibration field of the pressure adjuster (colour of the spring): gas
train MBC-1900-SE.
The losses of load along the gas supply line are indicated in Appendix C.
See the accompanying instructions for the adjustment of
the gas train.
D722
Fig. 19
WARNING
P2
5
6B
8
8
6A
P2
P1
P1
13
12
10
12
10
1
2
3
4
7
9
1
2
3
4
7
13
11
11
L1 L
L1 L
P3
D3735
1 - Gas input pipe
2 - Manual valve
3 - Vibration damping joint
4 - Pressure gauge with pushbutton cock
5 - Filter
6A - “Threaded” multibloc including:
- filter (can be replaced)
- safety valve
- working valve
- pressure adjuster
6B - “Flanged” multibloc including:
- safety valve
- working valve
- pressure adjuster
7 - Minimum gas pressure switch
8 - Valve leak detection control device.
In accordance with the standard EN 676,
leak detection is compulsory for burners with
maximum outputs of more than 1200 kW.
9-Gasket
10 - Gasket supplied with burner
11 - Gas adjustment butterfly valve
12 - Maximum gas pressure switch
13 - Gas train/burner adaptor
- supplied with burner
- supplied on request separately from the
gas train for the flanged versions
P1 - Pressure at combustion head
P2 - Upstream pressure of valves/adjuster
P3 - Pressure upstream from the filter
L - Gas train supplied separately with the
code indicated in Appendix B.
L1 - The responsibility of the installer
Fig. 20